溫控儀表的電流輸出有什么區別?
時間:2020-01-15
作者(zhe):互聯網
閱讀:7312
在使(shi)用溫控儀表的(de)(de)時(shi)候,都會選擇不同(tong)的(de)(de)控制輸(shu)出,常用的(de)(de)有(you)繼電(dian)器(qi)輸(shu)出,固態繼電(dian)器(qi)輸(shu)出,電(dian)流輸(shu)出等(deng)。不同(tong)的(de)(de)輸(shu)出,外面所(suo)接到(dao)中間轉換器(qi)也(ye)是(shi)不一樣(yang)的(de)(de)。當然所(suo)產生的(de)(de)控制效(xiao)果(guo)(guo)也(ye)不一樣(yang),一般(ban)可控硅移向輸(shu)出的(de)(de)控制效(xiao)果(guo)(guo)相對好點。那(nei)么溫控儀表的(de)(de)電(dian)流輸(shu)出有(you)那(nei)些呢?它們之間又有(you)什么不同(tong)呢?
溫控(kong)(kong)(kong)儀表的電(dian)(dian)(dian)流(liu)輸(shu)出(chu)可以(yi)分(fen)成控(kong)(kong)(kong)制電(dian)(dian)(dian)流(liu)和變送電(dian)(dian)(dian)流(liu)。控(kong)(kong)(kong)制電(dian)(dian)(dian)流(liu)是恒溫控(kong)(kong)(kong)制,比如溫度(du)控(kong)(kong)(kong)制在200度(du),開始的時(shi)候電(dian)(dian)(dian)流(liu)是20mA的輸(shu)出(chu)。隨著溫度(du)接近(jin)200度(du)的時(shi)候,電(dian)(dian)(dian)流(liu)逐漸(jian)減小(xiao),可能電(dian)(dian)(dian)流(liu)在8mA時(shi)候能夠恒溫。這個控(kong)(kong)(kong)制一般(ban)控(kong)(kong)(kong)制電(dian)(dian)(dian)磁閥(fa)。
如果(guo)你使用控制電流,那么就要選擇XMTA-908系列的(de)智能溫(wen)(wen)控儀表(biao)。變送電流,是根據你的(de)溫(wen)(wen)度(du)(du)范圍,變送輸出(chu)4-20mA。例如你的(de)溫(wen)(wen)度(du)(du)范圍是0-200度(du)(du),輸出(chu)4-20mA,那么0度(du)(du)的(de)時候對(dui)應4mA,200度(du)(du)的(de)時候對(dui)應20mA,中(zhong)(zhong)間程線性。變送輸出(chu)的(de)一般(ban)常用在變頻器中(zhong)(zhong)。如果(guo)你要使用變送電流,那么久要選擇XMTA-808系列的(de)智能溫(wen)(wen)控儀表(biao)。
在(zai)使用智能溫控(kong)儀中,它的(de)參數有(you)是如何設(she)(she)(she)置呢?任(ren)意規(gui)格線(xian)性電流輸出(chu)(chu)(chu)時(OP-A=1):輸出(chu)(chu)(chu)上限及(ji)輸出(chu)(chu)(chu)下限定(ding)義儀表的(de)電流輸出(chu)(chu)(chu)規(gui)格,范(fan)圍(wei)在(zai)0-22mA之間任(ren)意設(she)(she)(she)置。如0-20mA輸出(chu)(chu)(chu)則設(she)(she)(she)置outL=0,outH=200(單位0.1mA)。4-20mA設(she)(she)(she)置為outL=40,outH=200。也可定(ding)義成非標準(zhun)的(de)輸出(chu)(chu)(chu),如2-10mA輸出(chu)(chu)(chu),設(she)(she)(she)置outL=20,outH=100等。注意設(she)(she)(she)置outL必須(xu)小(xiao)于outH才能有(you)有(you)效的(de)輸出(chu)(chu)(chu)。(僅供參考)
控制電流(liu)輸出和(he)變送(song)電流(liu)輸出的溫(wen)控儀(yi)表是不一樣的,所以用戶一定(ding)要(yao)正(zheng)確的選擇(ze),不然購買來是不能(neng)正(zheng)常的使用哦。